| Total building area: |
213,444 sq. ft., six story building |
| Available floor: |
5th Floor - Leased, 6th Floor – Under contract
Additional floors will become available for occupancy in 2nd Q 2002.
|
| Floor Loading: |
200 lb/sq. ft. (all floors meet or exceed this load bearing capability) |
| Clear Heights: |
All slab-to-slab heights meet or exceed 19 ft. Clear heights meet or exceed the 17 ft. range |
| Loading Dock: |
Six loading docks with ample room for large truck deliveries |
| Elevators: |
Four (3 ton each) freight elevators and four passenger elevators (two in each lobby) |
| Column spacing: |
Approximately 40 ft. by 35 ft. - excellent floor layout |
| Generator: |
400KVA for life support activities and currently has spare capacity with up to 8 hours fuel supply |
| Security: |
7x24 coverage with cameras at all entrances and lobbies. |
| Parking: |
104 cark park in the basement |
| Riser space: |
Telephone riser and an empty data riser - enough for 4" conduits. Also, large electrical riser space available. |
| Generator space: |
One locked room that comprises 800 sq. ft is available. |
| Fuel tanks: |
There is space outside for a large buried fuel tanks. |
| Network: |
This location is close to major ROWs and there are a number of carriers in the area - Starhub, Singtel, and SCV |
| Building Access: |
A cable chamber outside on the ground floor designed to provide penetration into the building membrane. |
| Power: |
A 15MVA utility feed is available with dual feeds into the building. |
| Power topology: |
Building is 1.5 kilometers from sub station. All utility services are ring fed and power station has redundant power feeds from main grid. |
| Roof space: |
Good loading and currently has satellite dishes and chiller plant, with plenty of room for growth. |